Standalone Gas Detectors

Detectors

The GS-220.BC.V analogue combustible gas detectors monitor hydrocarbons, organic solvents, hydrogen, natural gas, LPG, and other combustible gases using catalytic, semiconductor, or electrochemical sensors, feature self-diagnostics for continuous monitoring of sensor and signal lines with fault alerts, remote magnetic key calibration without opening the enclosure for easy maintenance, and are housed in an IP65-rated metal enclosure.

Stand Alone Carbon Monoxide Detector

  • The CO-200 is the new stand alone CO
    detector from Zeta Alarm Systems. It has
    been designed with the same dimensions as
    a standard 2 gang fi tting, so can be installed
    either Surface mounted with it’s own backbox,
    or with a standard recessed box for semi-fl ush
    mounting.
  • It can be powered either from 230V AC mains,or from a DC supply (9-28V DC).
  • It has a built in bar graph display to show thecurrent CO level reading, and has a 2 stagerelay output which operates at fi rst alarm level(100ppm) & second alarm level (200ppm).
  • It has a built in bar graph display to show the current CO level reading, and has a 2 stage relay output which operates at first alarm level (100ppm) & second alarm level (200ppm).
  • There is also a 5 volt alarm output capable of supplying 200mA.
  • It has power, fault & alarm indications, as well as a control button for mute (press) and reset (Press & hold for 5 seconds)

Stand Alone Combustible Gas Detector

  • The ZG-100 is the new stand alone Combustible
    Gas detector from Zeta Alarm Systems. It has been
    designed with the same dimensions as a standard
    2 gang fi tting, so can be installed either Surface
    mounted with it’s own backbox, or with a standard
    recessed box for semi-fl ush mounting.
  • There are two versions available. One calibrated for Natural gas, one calibrated for LPG. They can be powered either from 230V AC mains, or from a DC supply (9-28V DC).
  • They have a built in bar graph display to show the current Gas level as a %LEL reading, and has a 2 stage relay output which operates at fi rst alarm level (10%LEL) & second alarm level (25%LEL). There is also a 5 volt alarm output capable of supplying 200mA.
  • They have power, fault & alarm indications, as well as a control button for mute (press) and reset (Press & hold for 5 seconds).